Heating and cooling system for multi reactors

The whole system we adopt is fully closed piping design, high efficiency plate heat exchanger used to reduce the demand of thermal fluid as well as greatly increase utilization of heat in order to achieve rapid ups and downs in temperature. The system with an expansion vessel, and the heatconducting medium in the expansion vessel does not participate in liquid circulation, whatever the temperature is high temperature or low temperature, the expansion tank is limited to 60°C. The working life and properties of the thermal fluid are also protected, by avoiding direct contact between the hot fluid and atmosphere.

Overview

  • Working temperature rang from -100 °C to +300 °C.
  • Centralized control of 3~20 reactors, each reactor’s material temperature and jacket temperature can be set independently. One system control multiple reactors of target temperature is realized.
  • Maximum process stability and reproducibility.
  • Under the system control, energy-saving efficiency is improved.The freezing medium and heating medium flowing through the conduction angle of the reactors are controlled accurately.
  • Previously unachievable performance.
  • High-accuracy and intelligent temperature control.
  • Adopt Plate heat exchanger & Piping heater to improve the heating and cooling rates.
  • High Cooling Power from 0.5 to 400 kW.
  • Factory’s existing refrigeration system and heating system can be used together with this system in order to reduce the input cost.
  • Large temperature range without fluid change.
  • Increased thermal fluid life.
  • 10 inch TFT touchscreen with graphic display.
  • Comprehensive warning and safety functions.
  • Rapid cooling down from high temperature (from 300 °C).
  • Using Magnetic drive pump with no leakage of the shaft seal.
  • With USB interfaces, RS485 interfaces, industrial control configuration software.
  • It can be produced explosion-proof function according to customer’s requirement.

Specifications

TCU LAB MODELS

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-320 -30 °C ~ +180 °C 2 kW 1.5 kW @ 0°C AC 220V 50Hz;
2.9 kW max
Air cooled machine
TCU-420W -38 °C ~ +180 °C 2 kW 1.8 kW @ 0°C AC 220V 50Hz;
3.3 kW max
Water cooled machine
TCU-430W -40 °C ~ +200 °C 3 kW 3 kW @ 0°C AC 380V 50Hz;
5 kW max
Water cooled machine

TCU-1 SERIES (-10 DegC ~ +150 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-125W -10 °C ~ +150 °C 2.5 kW 1.5 kW @ -5°C AC 220V 50Hz;
4 kW max
Options available for air cooled and water cooled machines
TCU-135W -10 °C ~ +150 °C 3.5 kW 2.1 kW @ -5°C 380V 50Hz;
5.6 kW max
TCU-155W -10 °C ~ +150 °C 5.5 kW 3.3 kW @ -5°C 380V 50Hz;
8 kW max
TCU-175W -10 °C ~ +150 °C 7.5 kW 4.2 kW @ -5°C 380V 50Hz;
10.5 kW max
TCU-1A10W -10 °C ~ +150 °C 10 kW 6 kW @ -5°C 380V 50Hz;
13.8 kW max
TCU-1A15W -10 °C ~ +150 °C 15 kW 9 kW @ -5°C 380V 50Hz;
20 kW max

TCU-2 SERIES (-25 DegC ~ +200 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-225W -25 °C ~ +200 °C 2.5 kW 2 kW @ -5°C AC 220V 50Hz;
4 kW max
Options available for air cooled and water cooled machines
TCU-235W -25 °C ~ +200 °C 3.5 kW 3 kW @ -5°C 380V 50Hz;
5.6 kW max
TCU-255W -25 °C ~ +200 °C 5.5 kW 4.5 kW @ -5°C 380V 50Hz;
8 kW max
TCU-275W -25 °C ~ +200 °C 7.5 kW 6.6 kW @ -5°C 380V 50Hz;
11 kW max
TCU-2A10W -25 °C ~ +200 °C 10 kW 8 kW @ -5°C 380V 50Hz;
14 kW max
TCU-2A15W -25 °C ~ +200 °C 15 kW 12 kW @ -5°C 380V 50Hz;
21 kW max
TCU-2A25W -25 °C ~ +200 °C 25 kW 19 kW @ -5°C 380V 50Hz;
35 kW max
TCU-2A38W -25 °C ~ +200 °C 38 kW 30 kW @ -5°C 380V 50Hz;
54 kW max
Option for water cooled machine only
TCU-2A60W -25 °C ~ +200 °C 60 kW 46 kW @ -5°C 380V 50Hz;
81 kW max
TCU-2A95W -25 °C ~ +200 °C 95 kW 70 kW @ -5°C 380V 50Hz;
126 kW max
TCU-2A130W -25 °C ~ +200 °C 130 kW 80 kW @ -5°C 380V 50Hz;
165 kW max
TCU-2A200W -25 °C ~ +200 °C 200 kW 125 kW @ -5°C 380V 50Hz;
260 kW max

NOTE: Option available for machines with temp range from -25 °C to +300 °C

TCU-5 SERIES (-45 DegC ~ +250 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-535W -45 °C ~ +250 °C 3.5 kW 3 kW @ 0°C 380V 50Hz;
6.2 kW max
Options available for air cooled and water cooled machines
TCU-555W -45 °C ~ +250 °C 5.5 kW 5 kW @ 0°C 380V 50Hz;
9 kW max
TCU-575W -45 °C ~ +250 °C 7.5 kW 7 kW @ 0°C 380V 50Hz;
11.5 kW max
TCU-5A10W -45 °C ~ +250 °C 10 kW 10 kW @ 0°C 380V 50Hz;
16 kW max
TCU-5A15W -45 °C ~ +250 °C 15 kW 15 kW @ 0°C 380V 50Hz;
23 kW max
TCU-5A25W -45 °C ~ +250 °C 25 kW 25 kW @ 0°C 380V 50Hz;
37 kW max
TCU-5A38W -45 °C ~ +250 °C 38 kW 38 kW @ 0°C 380V 50Hz;
55 kW max
TCU-5A60W -45 °C ~ +250 °C 60 kW 60 kW @ 0°C 380V 50Hz;
85 kW max
Option for water cooled machine only
TCU-5A95W -45 °C ~ +250 °C 95 kW 95 kW @ 0°C 380V 50Hz;
130 kW max
TCU-5A130W -45 °C ~ +250 °C 130 kW 130 kW @ 0°C 380V 50Hz;
178 kW max
TCU-5A200W -45 °C ~ +250 °C 200 kW 200 kW @ 0°C 380V 50Hz;
280 kW max

NOTE: Option available for machines with temp range from -45 °C to +300 °C

TCU-6 SERIES (-60 DegC ~ +250 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-625W -60 °C ~ +250 °C 2.5 kW 0.95 kW @ -40°C 380V 50Hz;
6.2 kW max
Options available for air cooled and water cooled machines
TCU-635W -60 °C ~ +250 °C 3.5 kW 1.45 kW @ -40°C 380V 50Hz;
6.2 kW max
TCU-655W -60 °C ~ +250 °C 5.5 kW 2.3 kW @ -40°C 380V 50Hz;
9 kW max
TCU-675W -60 °C ~ +250 °C 7.5 kW 3.1 kW @ -40°C 380V 50Hz;
11.5 kW max
TCU-6A10W -60 °C ~ +250 °C 10 kW 4.8 kW @ -40°C 380V 50Hz;
16 kW max
TCU-6A15W -60 °C ~ +250 °C 15 kW 7.8 kW @ -40°C 380V 50Hz;
23 kW max
Option for water cooled machine only
TCU-6A25W -60 °C ~ +250 °C 25 kW 18 kW @ -40°C 380V 50Hz;
37 kW max
TCU-6A38W -60 °C ~ +250 °C 38 kW 23 kW @ -40°C 380V 50Hz;
55 kW max
TCU-6A60W -60 °C ~ +250 °C 60 kW 31 kW @ -40°C 380V 50Hz;
85 kW max

TCU-7 SERIES (-70 DegC ~ +250 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-725W -70 °C ~ +250 °C 2.5 kW 0.4 kW @ -60°C 380V 50Hz;
5.8 kW max
Options available for air cooled and water cooled machines
TCU-735W -70 °C ~ +250 °C 3.5 kW 0.55 kW @ -60°C 380V 50Hz;
8 kW max
TCU-755W -70 °C ~ +250 °C 5.5 kW 0.75 kW @ -60°C 380V 50Hz;
11 kW max
TCU-775W -70 °C ~ +250 °C 7.5 kW 0.9 kW @ -60°C 380V 50Hz;
14 kW max
TCU-7A10W -70 °C ~ +250 °C 10 kW 1.2 kW @ -60°C 380V 50Hz;
19 kW max
Water cooled machines
TCU-7A15W -70 °C ~ +250 °C 15 kW 2.8 kW @ -60°C 380V 50Hz;
28 kW max

TCU-8 SERIES (-80 DegC ~ +250 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-825W -80 °C ~ +250 °C 3 kW 1 kW @ -60°C 380V 50Hz;
7.5 kW max
Water cooled machines
TCU-835W -80 °C ~ +250 °C 3.5 kW 1.4 kW @ -60°C 380V 50Hz;
9 kW max
TCU-855W -80 °C ~ +250 °C 5.5 kW 1.6 kW @ -60°C 380V 50Hz;
12 kW max
TCU-875W -80 °C ~ +250 °C 7.5 kW 3 kW @ -60°C 380V 50Hz;
17 kW max
TCU-8A10W -80 °C ~ +250 °C 10 kW 3.5 kW @ -60°C 380V 50Hz;
22 kW max
TCU-8A15W -80 °C ~ +250 °C 15 kW 5.8 kW @ -60°C 380V 50Hz;
32 kW max
TCU-8A25W -80 °C ~ +250 °C 25 kW 10 kW @ -60°C 380V 50Hz;
54 kW max
TCU-8A38W -80 °C ~ +250 °C 38 kW 16 kW @ -60°C 380V 50Hz;
82 kW max
TCU-8A60W -80 °C ~ +250 °C 60 kW 23 kW @ -60°C 380V 50Hz;
130 kW max
TCU-8A80W -80 °C ~ +250 °C 80 kW 32 kW @ -60°C 380V 50Hz;
177 kW max

TCU-9 SERIES (-90 DegC ~ +250 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-925W -90 °C ~ +250 °C 3 kW 2.5 kW @ 0°C 380V 50Hz;
7.5 kW max
Water cooled machines
TCU-935W -90 °C ~ +250 °C 3.5 kW 3.5 kW @ 0°C 380V 50Hz;
11 kW max
TCU-955W -90 °C ~ +250 °C 5.5 kW 5.5 kW @ 0°C 380V 50Hz;
13 kW max
TCU-975W -90 °C ~ +250 °C 7.5 kW 7.5 kW @ 0°C 380V 50Hz;
16 kW max
TCU-9A10W -90 °C ~ +250 °C 10 kW 10 kW @ 0°C 380V 50Hz;
21 kW max
TCU-9A15W -90 °C ~ +250 °C 15 kW 15 kW @ 0°C 380V 50Hz;
32 kW max
TCU-9A25W -90 °C ~ +250 °C 25 kW 25 kW @ 0°C 380V 50Hz;
53 kW max
TCU-9A38W -90 °C ~ +250 °C 38 kW 38 kW @ 0°C 380V 50Hz;
76 kW max
TCU-9A60W -90 °C ~ +250 °C 60 kW 60 kW @ 0°C 380V 50Hz;
130 kW max
TCU-9A80W -90 °C ~ +250 °C 80 kW 80 kW @ 0°C 380V 50Hz;
170 kW max

TCU-10 SERIES (-100 DegC ~ +100 DegC)

Model Name Machine Outlet Temp Range Heating Power Cooling Power Power Supply Remarks
TCU-1035W -100 °C ~ +100 °C 3.5 kW 3.5 kW @ 0°C 380V 50Hz;
11 kW max
Water cooled machines
TCU-1055W -100 °C ~ +100 °C 5.5 kW 5.5 kW @ 0°C 380V 50Hz;
16 kW max
TCU-1075W -100 °C ~ +100 °C 7.5 kW 7.5 kW @ 0°C 380V 50Hz;
20 kW max
TCU-10A10W -100 °C ~ +100 °C 10 kW 10 kW @ 0°C 380V 50Hz;
26 kW max
TCU-10A15W -100 °C ~ +100 °C 15 kW 15 kW @ 0°C 380V 50Hz;
38 kW max
TCU-10A25W -100 °C ~ +100 °C 25 kW 25 kW @ 0°C 380V 50Hz;
58 kW max
TCU-10A38W -100 °C ~ +100 °C 38 kW 38 kW @ 0°C 380V 50Hz;
82 kW max
TCU-10A60W -100 °C ~ +100 °C 60 kW 60 kW @ 0°C 380V 50Hz;
135 kW max
TCU-10A80W -100 °C ~ +100 °C 80 kW 80 kW @ 0°C 380V 50Hz;
200 kW max
These are general specifications, it may deviate as per client’s requirement or at detailing stage.
Copyright © 2016 jagdamba-enterprise.in. All rights reserved.